TherMOOstat Wrangler
Enrichment Preview — for UC Davis Facilities Live output from the production Airtable base · before → after on real complaints.

What enrichment does to a comfort complaint

This is the actual output of TherMOOstat Wrangler, on the live UC Davis Facilities Airtable base. Left is the complaint as the student submitted it; right is the same record after enrichment — the original feedback kept intact, plus the room's full mechanical-notes history, its equipment, conditions, and a live BMS view. Every one of 29,258 complaints (2016–2026) now carries a record like these.

What the team asked for — now automatic on every ticket
  1. Every prior mechanical note for that room (or, if the room has none, the rest of the floor).
  2. The room's temperature vs. set-point and the outside air temp.
  3. The exact VAV → AHU serving it, plus a live BMS / drawing view.

1. Vet Med 3A (Multi-Purpose Teaching) 2110 — "Hot"

Real record · rec00hYMkrt6rJTeO · Submitted 2023-09-22 · Reporter: Hrair

Before Feedback · what the student submitted
Building
Vet Med 3A — Multi-Purpose Teaching
Room
2110
Comfort
Hot
Everything else
— blank
After enrichment the same record, enriched
Building / Room
Vet Med 3A — MPT · 2110  CAAN 4857
Comfort
Hot
Conditions
Room 69.5 °F · heat SP 67 / cool SP 71 · Within deadband
Equipment / control
AHU-6 · Siemens BAS
All mechanical notes — this room (37 on record)
2026-01-12 · Cold · Grace: "There was an issue this morning, found and worked on. Asked Hiroko — already known."
2026-01-05 · Cold · Rachel: "T1=60, T2=61, T3=63. Heating was at 100%, room trying hard to heat. Now ~70."
2024-09-25 · Hot · Joseph: "Supplied by AHU-6, fan inop, maintenance notified."
2024-09-24 · Hot · Jiaxin: "AHU-6 fan inop, maintenance already knows."
Live BMS — the serving air handler (AHU-6)
Vet Med 3A AHU-6 BMS control screen
AHU-6: supply fan ON 100%, OA 95 °F, supply air 58.8 °F, cooling valve 11% — the unit the notes flagged.
What changed: the complaint arrives tied to AHU-6, the room's whole note history (fan flagged inoperative, the heating-stuck event) is right there, and the live BMS screen is one click away.

2. Bainer Hall 1065 — "Chilly"

Real record · rec022KKpPJluJ87S · Submitted 2025-11-12 · Reporter: Hayley

Before Feedback · what the student submitted
Building
Roy Bainer Hall
Room
1065
Comfort
Chilly
Everything else
— blank
After enrichment the same record, enriched
Building / Room
Roy Bainer Hall · 1065  CAAN 4004
Comfort
Chilly
Conditions
Room 73.8 °F · heat SP 72 / cool SP 75 · outside 69 °F · Within deadband
Equipment
VAV 125 → AHU A/C-1 · Siemens BAS
All mechanical notes — this room (22 of 30 tickets)
2025-12-08 · Hot · Hayley: "Served by AC-4. Collin confirmed the Room-Temp point reflects 1065… Collin and Hiroko visited and found cubicles heat unevenly due to vent positioning."
2026-01-15 · Chilly · Yasmin: "Nothing wrong with the equipment last visit. Room temp doesn't drop below 70."
2026-03-13 · Warm · Hayley: "Office-cubicle room, uneven cooling/heating. Changed cooling set-point 75 → 74."
2026-04-17 · Chilly · Yasmin: "Set-points already on the upper range; supply air 69 °F at submission. Could raise but it may affect other rooms — emailing the occupant."
Past cases
30 in this room · 22 carry mechanical notes · 37% had a recorded response
What changed: exact unit (VAV 125 → AHU A/C-1), in band, and a documented cubicle-airflow case the team already visited and adjusted — no rediscovery, no duplicate truck-roll.

3. Mathematical Sciences 2125 — "Stuffy" · a real fault in the trail

Real record · rec0HCn7knf1JXuGT · Submitted 2025-10-01 · Reporter: Benjamin

Before Feedback · what the student submitted
Building
Mathematical Sciences Building
Room
2125
Comfort
Hot
Comment
Room is stuffy and fairly uncomfortable to work in.
After enrichment the same record, enriched
Building / Room
Mathematical Sciences · 2125  CAAN 4821
Comfort · Comment
Hot  "Room is stuffy and fairly uncomfortable to work in."
Conditions
Room 74.75 °F · heat SP 70 / cool SP 74 · outside 75.8 °F · just over cool SP
Equipment
AHU-3 · Siemens BAS (Desigo)
All mechanical notes — this room (13 of 14 tickets)
2025-10-02 · Hot · Benjamin: "AHU-3 supply temp meeting set-point. HHW valve not actuating — Tririga task 2873872 sent to controls. Room had max airflow, reheat off, SAT ~60 — doing everything it could to cool the zone. Math Science having COM issues."
2022-05-23 · Hot · Benjamin: "Currently 84 °F inside — room was unoccupied until 1:03."
2022-04-03 · Hot · Benjamin: "AHU-3 scheduled to run 11–3. Room is 83.6 °F."
Past cases
14 in this room (Hot 13) · 13 carry mechanical notes
What changed: this one's not just preference — the room runs over set-point, and the notes pin it to a heating-hot-water valve that isn't actuating (work order already in Tririga). The reviewer sees the open fault, not a blank box.

4. Olson Hall 147 — "Chilly" · exact unit + the drawing

Real record · rec01bQdkiY0VmnU0 · Submitted 2024-10-24 · Reporter: Serra

Before Feedback · what the student submitted
Building
Olson Hall
Room
147
Comfort
Chilly
Everything else
— blank
After enrichment the same record, enriched
Building / Room
Olson Hall · 147  CAAN 3803
Comfort
Chilly
Conditions
Room 70.3 °F · heat SP 70 / cool SP 74 · outside 70 °F · Within deadband
Equipment
FCU-1-47 → AHU-1 · Siemens BAS
Mechanical notes — this room
2017-04-03 · Hot · Emerald: "Issue with CHW to AHU. Corrected evening of 4/3." — the chilled-water-to-AHU theme recurs across Olson's floor and its 1,357 building tickets.
Drawing — diffusers & thermostat for this room
Olson Hall mechanical drawing — diffuser layout and relocated thermostat
Mechanical drawing: supply-diffuser layout and the relocated thermostat — explains uneven temps.
What changed: resolves to FCU-1-47 → AHU-1, in band, with the room's CHW note and the diffuser drawing pointing the tech at the loop and the layout.

Across all 29,258 complaints

Coverage
Original feedback kept, enriched with the room's full note history100%
Resolved to a specific VAV/AHU air-handler~34%
In a building with an identified control system93.5%
Canonical CAAN + building linkevery building
Time to enrich one record~30 seconds, no manual lookup

Today a reviewer opens a complaint with a building, a room, and a comfort vote. After TherMOOstat Wrangler, they open the same record — original feedback intact — now carrying the room's actual temperature vs. set-point and outside air, the exact VAV → AHU and its live BMS view, and every prior tech note for that room.